- CPX-AP-I-4AI-U-I-RTD-M12
- 8086606
- CPX-AP-I-4AI-U-I-RTD-M12
- By Festo
- FREE Shipping on orders of $1,000 or more
- FREE Lifetime Tech Support
Overview
Features
- 30 x 170 x 35 mm dimensions (W x l x h)
- On H-rail via accessories type of mounting
- With through-hole type of mounting
- 166G product weight
- -20GC ambient temperature
- 50GC ambient temperature
- 5 - 95% relative air humidity
- Non-condensing relative air humidity
- IP65 degree of protection
- IP67 degree of protection
- Unused connections sealed note on degree of protection
- 1 - Low corrosion stress corrosion resistance class cRC
- 30 m inputs max. cable length
- 50 m system communication max. cable length
- VDMA24364-B2-L lABS (PWIS) conformity
- To EU EMC Directive cE mark (see declaration of conformity)
- To UK instructions for EMC cE marking (see declaration of conformity)
- KC-EMV kC mark
- RCM trademark approval
- C UL us listed (OL) approval
- UL E239998 certificate issuing authority
- RoHS-compliant note on materials
- PA material housing
- PC material housing
- Die-cast zinc, nickel-plated material housing
- NBR material seals
- FPM material o-ring
- Diagnostics per module diagnostics via lED
- Status per channel diagnostics via lED
- Wire break diagnostics per internal communication
- Module error diagnostics per internal communication
- Short circuit/overload in sensor supply diagnostics per internal communication
- Parameter errors diagnostics per internal communication
- Parameterisation error diagnostics per internal communication
- Overload at analogue inputs diagnostics per internal communication
- Upper limit value violated diagnostics per internal communication
- Overflow/underflow diagnostics per internal communication
- Lower limit value not observed diagnostics per internal communication
- System communication XF10 IN / XF20 OUT communication interface, function
- 2x socket communication interface, connection type
- M8x1, D-coded according to EN 61076-2-114 communication interface, connection technology
- 4 communication interface, number of pins/wires
- AP communication interface, protocol
- Yes communication interface, shielding
- Incoming electronics/sensors and load power supply, function
- Plugs power supply, connection type
- M8x1, A-coded to EN 61076-2-104 power supply, connection system
- 4 power supply, number of pins/wires
- Outgoing electronics/sensors and load power transmission, function
- Socket power transmission, connection type
- M8x1, A-coded to EN 61076-2-104 power transmission, connection technology
- 4 power transmission, number of pins/wires
- SELV/PELV fixed power supplies required note regarding operating voltage
- Note voltage drop note regarding operating voltage
- 24V nominal dC operating voltage, electronics/sensors
- ± 25% permissible voltage fluctuations for electronics/sensors
- 2 x 4 A (external fuse required) max. power supply
- Typically 38 mA intrinsic current consumption at nominal operating voltage for electronics/sensors
- 10MS power failure bridging
- Yes reverse polarity protection
- Analogue input electrical connection input, function
- 4x socket electrical connection input, connection type
- M12x1, A-coded to EN 61076-2-101 electrical connection input, connector system
- To achieve compliance with the technical specifications, the opposite side must be screened and designed with gold contact surfaces. electrical connection input, note on connector system
- 5 electrical connection input, number of connections/cores
- 4 number of inputs
- Internal electronic fuse per module fuse protection of inputs (short circuit)
- 1A max. residual current of inputs per module
- No electrical isolation of inputs between channels
- Yes electrical isolation of inputs between channel - internal communication
- Voltage measured variable
- Current measured variable
- Temperature measured variable
- Resistor measured variable
- 15 bits + prefix data format
- Linear scaling data format
- -10 - 10 V analog input
- -5 - 5 V analog input
- 0 - 10 V analog input
- 0 - 20 mA analog input
- 0 - 500 Ohm analog input
- 1 - 5 V analog input
- 4 - 20 mA analog input
- ±0.025% at 25°C repetition accuracy
- ±0.1% for voltage basic error limit at 25 °C
- ±0.1% for current basic error limit at 25 °C
- ±0.2% for resistor basic error limit at 25 °C
- ±0.4% for temperature basic error limit at 25 °C
- ±0.15% for voltage operating error limit related to the ambient temperature range
- ±0.15% for current operating error limit related to the ambient temperature range
- ±0.35% for resistor operating error limit related to the ambient temperature range
- ±0.9% for temperature operating error limit related to the ambient temperature range
- -40GC to 70GC storage temperature