$721.28
  • SFAW-100T-TG34-E-PNLK-PNVBA-M12
  • 8036876

Overview

Features

  • 995566 symbol
  • RCM trademark approval
  • C UL us listed (OL) approval
  • To EU EMC Directive cE mark (see declaration of conformity)
  • In accordance with EU RoHS Directive cE mark (see declaration of conformity)
  • To UK instructions for EMC cE marking (see declaration of conformity)
  • To UK RoHS instructions cE marking (see declaration of conformity)
  • RoHS-compliant note on materials
  • Flow rate measured variable
  • Temperature measured variable
  • Unidirectional flow direction
  • P1 -> P2 flow direction
  • Flow: Vortex measurement method
  • Temperature: PT1000 measurement method
  • 5L2 start value for flow rate measuring range
  • 100L2 end value for flow rate measuring range
  • 0GC temperature measurement start value
  • 90GC temperature measurement end value
  • 0MPA operating pressure
  • 1.2MPA operating pressure
  • 0BAR operating pressure
  • 12BAR operating pressure
  • Max. 1.2 MPa (12 bar / 174 psi) at 40 °C note on operating pressure
  • Max. 0.6 MPa (6 bar / 87 psi) at 90 °C note on operating pressure
  • 4MPA overload pressure
  • 40BAR overload pressure
  • 580PSI overload pressure
  • Liquid media operating medium
  • Water operating medium
  • Neutral fluids operating medium
  • Media with a kinematic viscosity = 1.8 mm²/sec. [cSt]. Compatibility of the media with the substances in contact with the media must be ensured. note on operating and pilot medium
  • 0GC media temperature
  • 90GC media temperature
  • 23GC nominal temperature
  • ± 2% FS for flow rate <= 50% FS accuracy of flow rate
  • ± 3% of measured value for flow rate >= 50% FS accuracy of flow rate
  • 2GC accuracy temperature in ± °C
  • < ± 0.5% FS for flow rate <= 50% FS repetition accuracy of flow rate
  • < ± 1% o.m.v. for flow rate >= 50% FS repetition accuracy of flow rate
  • Typ. ± 0.05%FS/K temperature coefficient span in ± %FS/K
  • 2 x PNP or 2 x NPN, switchable switching output
  • Window comparator switching function
  • Threshold value comparator switching function
  • Freely programmable switching function
  • N/C or N/O contact, switchable switching element function
  • 100MA max. output current
  • 0 - 10 V analogue output
  • 4 - 20 mA analogue output
  • 1 - 5 V analogue output
  • 0L2 flow characteristic curve start value
  • 100L2 flow characteristic curve end value
  • 0GC temperature characteristic curve start value
  • 100GC temperature characteristic curve end value
  • 500OHM max. load resistance current output
  • 15KOH min. load resistance voltage output
  • Yes short circuit current rating
  • Available overload protection
  • IO-Link® protocol
  • Device V 1.1 iO-Link, protocol version
  • Smart sensor profile iO-Link, profile
  • Binary data channel (BDC) iO-Link, function classes
  • Process data variable (PDV) iO-Link, function classes
  • Identification iO-Link, function classes
  • Diagnostics iO-Link, function classes
  • Teach channel iO-Link, function classes
  • COM2 (38.4 kBaud) iO-Link, communication mode
  • Yes iO-Link, sIO-Mode support
  • A iO-Link, port class
  • 0 bytes iO-Link, process data length oUT
  • 5 bytes iO-Link, process data length iN
  • 1 bit BDC (temperature monitoring) iO-Link, process data content iN
  • 1 bit BDC (volume monitoring) iO-Link, process data content iN
  • 14 bit PDV (measured flow value) iO-Link, process data content iN
  • 14 bit PDV (measured temperature value) iO-Link, process data content iN
  • 2 bit BDC (flow monitoring) iO-Link, process data content iN
  • 32-bit volume measurement iO-Link, service data iN
  • 5 ms iO-Link, min. cycle time
  • 500KB iO-Link, data storage required
  • 18V operational voltage range dC
  • 30V operational voltage range dC
  • For all electrical connections reverse polarity protection
  • Plugs electrical connection 1, connection type
  • M12x1, A-coded to EN 61076-2-101 electrical connection 1, connector system
  • 5 electrical connection 1, number of connections/cores
  • Screw-type lock electrical connection 1, type of mounting
  • 995383 electrical connection 1, connection pattern
  • 20 m with IO-Link® operation max. cable length
  • 30 m max. cable length
  • Optional mounting position
  • Female thread G3/4 fluid connection
  • 530G product weight
  • PA-reinforced material housing
  • EPDM (peroxide) material in contact with the medium
  • ETFE material in contact with the medium
  • Stainless steel material in contact with the medium
  • PA6T/6I reinforced material in contact with the medium
  • US gal displayable units
  • US gal/min displayable units
  • Cft displayable units
  • Cft/min displayable units
  • L displayable units
  • L/h displayable units
  • L/min displayable units
  • M3 displayable units
  • °C displayable units
  • °F displayable units
  • IP65 degree of protection
  • 3 - high corrosion stress corrosion resistance class cRC
  • VDMA24364-B2-L lABS (PWIS) conformity
  • 0GC ambient temperature to 50GC ambient temperature